Operating voltage KNX |
Bus voltage, ≤4 mA |
Operating voltage |
110 V AC – 240 V AC, 50 Hz – 60 Hz |
Frequency |
50 – 60 Hz |
Stand-by consumption |
~0.3 W |
Capacity loss max. |
6.4 W |
Installation type |
DIN rail |
Width |
4 modules |
Type of connection |
Terminal screws | Bus connection: KNX bus terminal |
Max. cable cross section |
Solid wire: 0.5 mm² (Ø 0.8) to 6 mm² | Stranded wire with end sleeve: 0.5 mm² to 4 mm² |
Number of channels |
8 |
Type of contact |
NO contact, 16 A, 3 A |
Opening width |
< 3 mm |
Incandescent/halogen lamp load |
2000 W |
Fluorescent lamp load (conventional) parallel-corrected |
1300 W (140 µF) |
Fluorescent lamp load (conventional) not corrected |
2000 VA |
Fluorescent lamp load (electronic ballast) |
1200 W |
Energy saving lamps |
300 W |
LED lamp < 2 W |
55 W |
LED lamp 2-8 W |
600 W |
LED lamp > 8 W |
600 W |
Inrush current |
max. 800 A / 200 µs |
Voltage output |
240 V AC |
Switching output |
Potential-free |
Switching of various phases |
Possible |
Suitable for SELV |
Yes if all channels switch at SELV |
C load |
|
Type |
Base module |
Ambient temperature |
-5°C … 45°C |
Type of protection |
IP 20 |
Protection class |
II according to EN 60 669 |